H07V-U &H07V-R
Single-core non-sheathed cable with rigid conductor for general purposes & Single-core non-sheathed cable with solid conductor for internal wiring for a conductor temperature of 70 °C
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
IEC 60227-3
60227 IEC 05 ( H05V – U )
60227 IEC 01 ( H07V – U )
60227 IEC 01 ( H07V- R )
– 30℃ to + 70℃
CU/PVC
Annealed copper conductor
PVC/ C
*
*
*
According to the customer’s request
*
1- Outdoor lighting installations.
2- EarthingIndoor or receiver installations.
3- Indoor installations in housing.
Nominal cross section of conductors (mm²) | Conductor class | The number and diameter of the nominal string of conductors | Nominal insulation thickness (mm) | Average overall dimensions (Lower limit) (mm) | Average overall dimensions (Upper limit) (mm) | Maximum ohmic resistance of the conductor at 20°C (Ω/km) | The weight of a hundred meter coil (Kg) |
---|---|---|---|---|---|---|---|
0.5 | 1 | 1×0.8 | 0.6 | 1/9 | 2/3 | 36 | 8 |
0.75 | 1 | 1×0.95 | 0.6 | 2.1 | 2.5 | 24.5 | 11 |
1 | 1 | 1×1.12 | 0.6 | 2.2 | 2.7 | 18.1 | 13 |
1.5 | 1 | 1×1.33 | 0.7 | 2.6 | 3.2 | 12.1 | 19 |
1.5 | 2 | 7×0.52 | 0.8 | 2.7 | 3.3 | 12.1 | 21 |
2.5 | 1 | 1×1.74 | 0.8 | 3.2 | 3.9 | 7.41 | 30 |
2.5 | 2 | 7×0.66 | 0.8 | 3.3 | 4 | 7.41 | 33 |
4 | 1 | 1×2.19 | 0.8 | 3.6 | 4.4 | 4.61 | 44 |
4 | 2 | 7×0.82 | 0.8 | 3.8 | 4.6 | 4.61 | 48 |
6 | 1 | 1×2.76 | 0.8 | 4.1 | 5 | 3.08 | 62 |
6 | 2 | 7×1.01 | 0.8 | 4.3 | 5.2 | 3.08 | 67 |
10 | 1 | 1×3.51 | 1 | 5.3 | 6.4 | 1.83 | 104 |
10 | 2 | 7×1.33 | 1 | 5.6 | 6.7 | 1.83 | 111 |
16 | 2 | 7×1.7 | 1 | 6.4 | 7.6 | 1.15 | 169 |
25 | 2 | 7×2.12 | 1.2 | 8.1 | 9.7 | 0.727 | 264 |
35 | 2 | 7×2.46 | 1.2 | 9 | 10.9 | 0.524 | 354 |