Light inflexible cables

Light Inflexible cable 005




Cenelec

H05VV-R & H05VV-U

Name in related standard

Sheathed cables for fixed wiring

Nominal Voltage U0/U

300/500V

Reference standard

IEC 60227-4

Standard code

60227 IEC 10

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.

PVC core insulation

Compound type of PVC/ C.

PVC outer sheath

Compound type of PVC/ ST4.

Filler

PVC

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black.

1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.

Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Approximate thickness of filler mm Nominal sheath thickness (mm) Average overall dimensions (Lower limit) (mm) Average overall dimensions (Upper limit) (mm) Maximum ohmic resistance of the conductor at 20°C (Ω/km) Approximate (weight kg/km)
2×1.5 1 1×1.33 0.7 0.6 1.2 7.6 10 12.1 115
2×1.5 2 7×0.52 0.7 0.6 1.2 7.8 10.5 12.1 124
2×2.5 1 1×1.74 0.8 0.6 1.2 8.6 11.5 7.41 155
2×2.5 2 7×0.66 0.8 0.6 1.2 9 12 7.41 169
2×4 1 1×2.19 0.8 0.6 1.2 9.6 12.5 4.61 200
2×4 2 7×0.82 0.8 0.6 1.2 10 13 4.61 220
2×6 1 1×2.76 0.8 0.6 1.2 10.5 13.5 3.08 260
2×6 2 7×1.01 0.8 0.6 1.2 11 14 1.08 285
2×10 1 1×3.51 1 0.7 1.4 13 16.5 1.83 430
2×10 2 7×1.33 1 0.7 1.4 13.5 17.5 1.83 455
2×16 2 7×1.7 1 0.7 1.4 15.5 20 1.15 630
2×25 2 7×2.12 1.2 1 1.4 18.5 24 0.727 960
2×35 2 7×2.46 1.2 1.1 1.6 21 27.5 0.524 1280
3×1.5 1 1×1.33 0.7 0.6 1.2 8 10.5 12.1 135
3×1.5 2 7×0.52 0.7 0.6 1.2 8.2 11 12.1 142
3×2.5 1 1×1.74 0.8 0.6 1.2 9.2 12 7.41 185
3×2.5 2 7×0.66 0.8 0.6 1.2 9.4 12.5 7.41 201
3×4 1 1×2.19 0.8 0.6 1.2 10 13 4.61 246
3×4 2 7×0.82 0.8 0.6 1.2 10.5 13.5 4.61 268
3×6 1 1×2.76 0.8 0.6 1.4 11.5 14.5 3.08 340
3×6 2 7×1.01 0.8 0.6 1.4 12 15.5 3.08 361
3×10 1 1×3.51 1 0.7 1.4 14 17.5 1.83 535
3×10 2 7×1.33 1 0.7 1.4 14.5 19 1.83 568
3×16 2 7×1.7 1 0.9 1.4 16.5 21.5 1.15 815
3×25 2 7×2.12 1.2 1 1.6 20.5 26 0.727 1230
3×35 2 7×2.46 1.2 1.1 1.6 22 29 0.524 1620
4×1.5 1 1×1.33 0.7 0.6 1.2 8.6 11.5 12.1 161
4×1.5 2 7×0.52 0.7 0.6 1.2 9 12 12.1 172
4×2.5 1 1×1.74 0.8 0.6 1.2 10 13 7.41 223
4×2.5 2 7×0.66 0.8 0.6 1.2 10 13.5 7.41 242
4×4 1 1×2.19 0.8 0.6 1.4 11.5 14.5 4.61 312
4×4 2 7×0.82 0.8 0.6 1.4 12 15 4.61 338
4×6 1 1×2.76 0.8 0.7 1.4 12.5 16 3.08 421
4×6 2 7×1.01 0.8 0.7 1.4 13 17 3.08 452
4×10 2 7×1.33 1 0.8 1.4 16 20.5 1.83 695
4×16 2 7×1.7 1 0.9 1.4 18 23.5 1.15 1000
4×25 2 7×2.12 1.2 1.1 1.6 22.5 28.5 0.727 1555
4×35 2 7×2.46 1.2 1.2 1.6 24.5 32 0.524 2010
5×1.5 1 1×1.33 0.7 0.6 1.2 9.4 12 12.1 187
5×1.5 2 7×0.52 0.7 0.6 1.2 9.8 12.5 12.1 202
5×2.5 1 1×1.74 0.8 0.6 1.2 11 14 7.41 266
5×2.5 2 7×0.66 0.8 0.6 1.2 11 14.5 7.41 280
5×4 1 1×2.19 0.8 0.7 1.4 12.5 16 4.61 384
5×4 2 7×0.82 0.8 0.7 1.4 13 17 4.61 415
5×6 1 1×2.76 0.8 0.8 1.4 13.5 17.5 3.08 510
5×6 2 7×1.01 0.8 0.8 1.4 14.5 18.5 3.08 540
5×10 1 1×3.51 1 0.8 1.4 17 21 1.83 782
5×10 2 7×1.33 1 0.8 1.4 17.5 22 1.83 830
5×16 2 7×1.7 1 1 1.6 20.5 26 1.15 1225
5×25 2 7×2.12 1.2 1.2 1.6 24.5 31.5 0.727 1860
5×35 2 7×2.46 1.2 1.3 1.6 27 35 0.524 2450


Edit Table

Cenelec

H05VV-R & H05VV-U

Name in related standard

Sheathed cables for fixed wiring

Nominal Voltage U0/U

300/500V

Reference standard

IEC 60227-4

Standard code

60227 IEC 10

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.

PVC core insulation

Compound type of PVC/ C.

PVC outer sheath

Compound type of PVC/ ST4.

Filler

PVC

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black.

1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.

[ninja_tables id=”18811″]

Flexible cables

Flexible cable 1




Cenelec

H05VV-F

Name in related standard

Ordinary PVC sheathed cord

Nominal Voltage U0/U

300/500 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 53

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor according to IEC 60228, class 5.

PVC core insulation

Compound type of PVC/ D.

PVC outer sheath

Compound type of PVC / ST5.

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black, white or as per customer request.

1-Indoor installations in housing.
2-Premises that contain a bath or shower.
3-These types of cables are used in applications such as extensions and connecting cables for electrical devices,
appliances and machinery where plugs must be permanently connected to the corresponding cables.
4-Any direct cable contact with hot parts of cooking and heating appliances and also any other heat influences is
prohibited.

Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Nominal sheath thickness (mm) Average overall dimensions (Lower limit) (mm) Average overall dimensions (Upper limit) (mm) Maximum ohmic resistance of the conductor at 20°C (ohm/km) Approximate weight (kg/km)
2×0.75 5 24×0.193 0.6 0.8 5.7 7.2 24.5 55
2×0.75 Flat 5 24×0.193 0.6 0.8 3.7×6 4.5×7.2 24.5 44
2×1 5 31×0.193 0.6 0.8 5.9 7.5 19.5 65
2×1 Flat 5 31×0.193 0.6 0.8 3.9×6.2 4.7×7.5 19.5 55
2×1.5 5 30×0.235 0.7 0.8 6.8 8.6 13.3 85
2×2.5 5 50×0.235 0.8 1 8.4 10.6 7.98 125
2×4 5 56×0.285 0.8 1.1 9.7 12.1 4.95 170
3×0.75 5 24×0.193 0.6 0.8 6 7.6 24.5 64
3×1 5 31×0.193 0.6 0.8 6.3 8 19.5 75
3×2.5 5 50×0.235 0.8 1.1 9.2 11.4 7.98 160
3×1.5 5 30×0.235 0.7 0.9 7.4 9.4 13.3 105
3×4 5 56×0.285 0.8 1.1 10.3 12.8 4.95 215
4×0.75 5 24×0.193 0.6 0.8 6.6 8.3 24.5 75
4×1 5 31×0.193 0.6 0.9 7.1 9 19.5 93
4×1.5 5 30×0.235 0.7 1 8.4 10.5 13.3 130
4×2.5 5 50×0.235 0.8 1.1 10.1 12.5 7.98 195
4×4 5 56×0.285 0.8 1.2 11.5 14.3 4.95 272
5×0.75 5 24×0.193 0.6 0.9 7.4 9.3 24.5 100
5×1 5 31×0.193 0.6 0.9 7.8 9.8 19.5 112
5×1.5 5 30×0.235 0.7 1.1 9.3 11.6 13.3 160
5×2.5 5 50×0.235 0.8 1.2 11.2 13.9 7.98 240
5×4 5 56×0.285 0.8 1.3 12.8 15.9 4.95 340


Edit Table

Cenelec

H05VV-F

Name in related standard

Ordinary PVC sheathed cord

Nominal Voltage U0/U

300/500 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 53

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor according to IEC 60228, class 5.

PVC core insulation

Compound type of PVC/ D.

PVC outer sheath

Compound type of PVC / ST5.

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black, white or as per customer request.

1-Indoor installations in housing.
2-Premises that contain a bath or shower.
3-These types of cables are used in applications such as extensions and connecting cables for electrical devices,
appliances and machinery where plugs must be permanently connected to the corresponding cables.
4-Any direct cable contact with hot parts of cooking and heating appliances and also any other heat influences is
prohibited.

[ninja_tables id=”18995″]

Light flexible cables

Light Inflexible cable 1




Cenelec

H03VV-F

Name in related standard

Light PVC sheathed cord

Nominal Voltage U0/U

300/300 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 52

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor
according to IEC 60228, class 5

PVC core insulation

Compound type of PVC /D

PVC outer sheath

Compound type of PVC / ST5

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are used as extensions and connecting cables for electrical devices,
2-appliances and machinery where plugs must be permanently connected to the corresponding cables.
Examples: kitchen utensils, desk lamps, floor lamps, vacuum cleaners, office machines, radios and etc. These cables are not permitted to be used for cooking or heating appliances, also they are not suitable for outdoor and industrial use or farming machinery.


Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Nominal sheath thickness (mm) Average overall dimensions (Lower limit) (mm) Average overall dimensions (Upper limit) (mm) Maximum ohmic resistance of the conductor at 20°C (ohm/km) Approximate weight (kg/km)
2×0.5 5 16×0.193 0.5 0.6 4.6 5.9 39 37
2×0.5 Flat 5 16×0.193 0.5 0.6 4.9×3 5.9×3.7 39 24
2×0.75 5 24×0.193 0.5 0.6 4.9 6.3 26 45
2×0.75 Flat 5 24×0.193 0.5 0.6 5.2×3.2 6.3×3.8 26 30
3×0.5 5 16×0.193 0.5 0.6 4.9 6.3 39 43
3×0.75 5 24×0.193 0.5 0.6 5.2 6.7 26 55


Edit Table

Cenelec

H03VV-F

Name in related standard

Light PVC sheathed cord

Nominal Voltage U0/U

300/300 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 52

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor
according to IEC 60228, class 5

PVC core insulation

Compound type of PVC /D

PVC outer sheath

Compound type of PVC / ST5

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are used as extensions and connecting cables for electrical devices,
2-appliances and machinery where plugs must be permanently connected to the corresponding cables.
Examples: kitchen utensils, desk lamps, floor lamps, vacuum cleaners, office machines, radios and etc. These cables are not permitted to be used for cooking or heating appliances, also they are not suitable for outdoor and industrial use or farming machinery.

[ninja_tables id=”18843″]

Circular Lift Cables

Circular 1




Cenelec

H05VV – F
H07VV – F

Name in related standard

Circular PVC sheathed lift cable and cable for flexible connections

Nominal Voltage U0/U

300 / 500 V for conductors up to and including 1mm²

450 / 750 V for conductors above 1mm²

Reference standard

IEC 60227-6

Standard code

۶۰۲۲۷ IEC 71C

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor according to IEC 60228, class 5.

PVC core insulation

Compound type of PVC/ D.

PVC outer sheath

Compound type of PVC / ST5.

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are often used as mobile cables for cranes, elevators and conveyor systems.
2- These cables are suitable for use in indoor facilities and their advantages include high flexibility and minimal space requirement.

Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Nominal diameter of insulation (mm) Assumed diameter wire (mm) K Assumed diameter under the sheath (mm) Nominal sheath thickness (mm) Average overall dimensions (mm) Maximum ohmic resistance of the conductor at 20°C (ohm/km) Approximate weight (kg/km)
2×1.5 5 30×0.235 0.7 3 1.4 2 5.6 1 8 13.3 88
2×2.5 5 50×0.235 0.8 3.6 1.8 2 6.8 1 9.2 7.98 125
2×4 5 56×0.285 0.8 4.2 2.3 2 7.8 1 10.4 4.95 165
2×6 5 84×0.285 0.8 4.8 2.8 2 8.8 1 11.6 3.3 216
2×10 5 144×0.285 1 6.1 3.6 2 11.2 1.3 14.8 1.91 380
2×16 5 224×0.285 1 7.2 4.5 2 13 1.3 17 1.21 512
2×25 5 301×0.306 1.2 8.8 5.6 2 16 1.6 20.8 0.78 731
3×2.5 5 50×0.235 0.8 3.6 1.8 2.16 7.3 1 9.8 7.98 158
3×4 5 56×0.285 0.8 4.2 2.3 2.16 8.4 1 11.1 4.95 212
3×6 5 84×0.285 0.8 4.8 2.8 2.16 9.5 1.3 13 3.3 290
3×10 5 144×0.285 1 6.1 3.6 2.16 12.1 1.3 15.8 1.91 493
3×16 5 224×0.285 1 7.2 4.5 2.16 14 1.3 18.2 1.21 712
3×25 5 301×0.306 1.2 8.8 5.6 2.16 17.3 1.6 22.2 0.78 1020
4×1.5 5 30×0.235 0.7 3 1.4 2.42 6.8 1 9.3 13.3 130
4×2.5 5 50×0.235 0.8 3.6 1.8 2.42 8.2 1 10.7 7.98 190
4×4 5 56×0.285 0.8 4.2 2.3 2.42 9.4 1.3 12.8 4.95 280
4×6 5 84×0.285 0.8 4.8 2.8 2.42 10.6 1.3 14.2 3.3 360
4×10 5 144×0.285 1 6.1 3.6 2.42 13.6 1.3 17.4 1.91 620
4×16 5 224×0.285 1 7.2 4.5 2.42 15.7 1.6 20.6 1.21 925
4×25 5 301×0.306 1.2 8.8 5.6 2.42 19.4 2 25.3 0.78 1310
5×1.5 5 30×0.235 0.7 3 1.4 2.7 7.6 1 10.1 13.3 156
5×2.5 5 50×0.235 0.8 3.6 1.8 2.7 9.2 1.3 12.3 7.98 245
5×4 5 56×0.285 0.8 4.2 2.3 2.7 10.5 1.3 13.9 4.95 340
5×6 5 84×0.285 0.8 4.8 2.8 2.7 11.9 1.3 15.6 3.3 445
5×10 5 144×0.285 1 6.1 3.6 2.7 15.1 1.6 19.7 1.91 750
5×16 5 224×0.285 1 7.2 4.5 2.7 17.6 1.6 22.6 1.21 1115
5×25 5 301×0.306 1.2 8.8 5.6 2.7 21.6 2 27.8 0.78 1570


Edit Table

Cenelec

H05VV – F
H07VV – F

Name in related standard

Circular PVC sheathed lift cable and cable for flexible connections

Nominal Voltage U0/U

300 / 500 V for conductors up to and including 1mm²

450 / 750 V for conductors above 1mm²

Reference standard

IEC 60227-6

Standard code

۶۰۲۲۷ IEC 71C

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor according to IEC 60228, class 5.

PVC core insulation

Compound type of PVC/ D.

PVC outer sheath

Compound type of PVC / ST5.

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are often used as mobile cables for cranes, elevators and conveyor systems.
2- These cables are suitable for use in indoor facilities and their advantages include high flexibility and minimal space requirement.

[ninja_tables id=”19002″]

Flexible Power Cables

Flexible Power 02




Cenelec

NYY R
NYY U

Name in related standard

Single Core Power Cables

Nominal Voltage U0/U

0.6/1 KV

Reference standard

IEC 60502 – 1

Standard code

IEC 60502 – 1

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Annealed copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ).

PVC core insulation

Compound type of PVC/ A.

PVC outer sheath

Compound type of PVC / ST1.

Filler

*

Shield

*

Core insulation color

Core insulation color is normally black.

Sheath color

Sheath color is normally black. According to the customer’s request.

These types of cables are used for distribution of electrical energy for fixed installations in underground, cable
ducts, indoors, in water and open air where mechanical damages are not expected.


Nominal cross section of conductors mm2 Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness mm Nominal diameter of insulation
mm
k Minimum sheath thickness
(mm)
Average overall dimensions
mm
Maximum ohmic resistance of the conductor at 20°C Ω/km
2*1.5 5 30*0.235 0.8 3.2 2 1.24 9.1 13.3
2*2.5 5 50*0.235 0.8 3.6 2 1.24 9.9 7.98
2*4 5 56*0.285 1 4.6 2 1.24 11.9 4.95
2*6 5 84*0.285 1 5.2 2 1.24 13.1 3.3
2*10 5 144*0.285 1 6.1 2 1.24 14.9 1.91
2*16 5 224*0.285 1 7.2 2 1.24 17.1 1.21
2*25 5 301*0.306 1.2 8.8 2 1.24 20.3 0.78
2*35 5 301*0.306 1.2 10.2 2.16 1.24 24.7 0.78
3*1.5 5 30*0.235 0.8 3.2 2.16 1.24 9.6 13.3
3*2.5 5 50*0.235 0.8 3.6 2.16 1.24 10.5 7.98
3*4 5 56*0.285 1 4.6 2.16 1.24 12.6 4.95
3*6 5 84*0.285 1 5.2 2.16 1.24 13.9 3.3
3*10 5 144*0.285 1 6.1 2.16 1.24 15.9 1.91
3*16 5 224*0.285 1 7.2 2.16 1.24 18.2 1.21
3*25 5 301*0.306 1.2 8.8 2.42 1.24 24.0 0.78
3*35 5 427*0.306 1.2 10.2 2.42 1.24 27.4 0.554
3*25/16 5 301*0.306 | 224*0.285 1.2-1 8.8-7.2 2.42 1.24 23.2 0.78-1.21
3*35/16 5 427*0.306 | 224*0.285 1.2-1 10.2-7.2 2.42 1.24 25.7 0.554-1.21
4*1.5 5 30*0.235 0.8 3.2 2.42 1.24 10.4 13.3
4*2.5 5 50*0.235 0.8 3.6 2.42 1.24 11.4 7.98
4*4 5 56*0.285 1 4.6 2.42 1.24 13.8 4.95
4*6 5 84*0.285 1 5.2 2.7 1.24 16.7 3.3
4*10 5 144*0.285 1 6.1 2.7 1.24 19.2 1.91
4*16 5 224*0.285 1 7.2 2.7 1.24 22.1 1.21
4*25 5 301*0.306 1.2 8.8 2.7 1.24 26.4 0.78
5*1.5 5 30*0.235 0.8 3.2 2.7 1.24 11.3 13.3
5*2.5 5 50*0.235 0.8 3.6 2.7 1.24 12.4 7.98
5*4 5 56*0.285 1 4.6 2.7 1.24 15.1 4.95
5*6 5 84*0.285 1 5.2 2.7 1.24 16.7 3.3
5*10 5 144*0.285 1 6.1 2.7 1.24 19.2 1.91
5*16 5 224*0.285 1 7.2 2.7 1.24 22.1 1.21
5*25 5 301*0.306 1.2 8.8 2.7 1.24 26.4 0.78


Edit Table

Cenelec

NYY R
NYY U

Name in related standard

Single Core Power Cables

Nominal Voltage U0/U

0.6/1 KV

Reference standard

IEC 60502 – 1

Standard code

IEC 60502 – 1

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Annealed copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ).

PVC core insulation

Compound type of PVC/ A.

PVC outer sheath

Compound type of PVC / ST1.

Filler

*

Shield

*

Core insulation color

Core insulation color is normally black.

Sheath color

Sheath color is normally black. According to the customer’s request.

These types of cables are used for distribution of electrical energy for fixed installations in underground, cable
ducts, indoors, in water and open air where mechanical damages are not expected.

[ninja_tables id=”19058″]

Inflexible Power Cables

Inflexible power 01




Cenelec

NYY-O
NYY-J
NAYY-O
NAYY-J
NA2XY
N2XY

Name in related standard

Multi Core Power Cables

Nominal Voltage U0/U

0.6/1 KV

Reference standard

IEC 60502 – 1

Standard code

IEC 60502 – 1

Tempreture range

PVC: -30℃ to +70℃
XLPE: -40℃ to +90℃

Cable Layer Construction

Cu/PVC/PVC
AL/PVC/PVC
AL/XLPE/PVC

Conductor material

copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ) or class 5 ( flexible ).

PVC core insulation

Compound type of PVC / A or XLPE

PVC outer sheath

Compound type of PVC/ ST1.

Filler

PVC

Shield

*

Core insulation color

According to the customer’s request

Sheath color

Sheath color is normally black. According to the customer’s request.

These types of cables are used for distribution of electrical energy for fixed installations in underground, cable

ducts, power stations, indoors, in water and open air where mechanical damages are not expected.



Nominal cross section of conductors mm2 Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness mm Nominal diameter of insulation
mm
k Approximate thickness of filler
mm
Approximate diameter of filler
mm
Minimum sheath thickness
mm
Average overall dimensions
mm
Maximum ohmic resistance of the conductor at 20°C Ω/km
2*1.5 1 1*1.33 0.8 3.0 2 0.6 7.3 1.24 9.8 12.1
2*1.5 2 7*0.52 0.8 3.2 2 0.6 7.5 1.24 10.1 12.1
2*2.5 1 1*1.74 0.8 3.4 2 0.6 8.1 1.24 10.7 7.41
2*2.5 2 7*0.66 0.8 3.6 2 0.6 8.4 1.24 10.9 7.41
2*4 1 1*2.19 0.8 3.9 2 0.6 9.0 1.24 11.6 4.61
2*4 2 7*0.82 0.8 4.1 2 0.6 9.3 1.24 11.9 4.61
2*6 1 1*2.76 0.8 4.5 2 0.6 10.1 1.24 12.7 3.08
2*6 2 7*1.01 0.8 4.6 2 0.6 10.5 1.24 13.0 3.08
2*10 1 1*3.51 1 5.6 2 0.7 12.6 1.24 15.2 1.83
2*10 2 7*1.33 1 6.0 2 0.7 13.4 1.24 16.0 1.83
2*16 2 7*1.7 1 7.2 2.16 0.7 17.0 1.24 19.5 1.15
2*25 2 7*2.12 1.2 8.9 2.16 0.8 20.7 1.24 23.3 0.727
2*35 2 7*2.46 1.2 9.9 2.16 0.8 22.9 1.24 25.5 0.524
3*1.5 1 1*1.33 0.8 3.0 2.16 0.6 7.7 1.24 10.3 12.1
3*1.5 2 7*0.52 0.8 3.2 2.16 0.6 8.0 1.24 10.6 12.1
3*2.5 1 1*1.74 0.8 3.4 2.16 0.6 8.6 1.24 11.2 7.41
3*2.5 2 7*0.66 0.8 3.6 2.16 0.6 8.9 1.24 11.5 7.41
3*4 1 1*2.19 0.8 3.9 2.16 0.6 9.6 1.24 12.2 4.61
3*4 2 7*0.82 0.8 4.1 2.16 0.6 10.0 1.24 12.5 4.61
3*6 1 1*2.76 0.8 4.5 2.16 0.6 10.8 1.24 13.4 3.08
3*6 2 7*1.01 0.8 4.6 2.16 0.6 11.2 1.24 13.8 3.08
3*10 1 1*3.51 1 5.6 2.16 0.7 13.5 1.24 16.1 1.83
3*10 2 7*1.33 1 6.0 2.16 0.7 14.3 1.24 16.9 1.83
3*16 2 7*1.7 1 7.2 2.16 0.9 17.4 1.24 19.9 1.15
3*25 2 7*2.12 1.2 8.9 2.16 0.8 20.7 1.24 23.3 0.727
3*35 2 7*2.46 1.2 9.9 2.16 0.8 22.9 1.24 25.5 0.524
4*1.5 1 1*1.33 0.8 3.0 2.42 0.6 8.5 1.24 11.1 12.1
4*1.5 2 7*0.52 0.8 3.2 2.42 0.6 8.8 1.24 11.4 12.1
4*2.5 1 1*1.74 0.8 3.4 2.42 0.6 9.5 1.24 12.1 7.41
4*2.5 2 7*0.66 0.8 3.6 2.42 0.6 9.9 1.24 12.4 7.41
4*4 1 1*2.19 0.8 3.9 2.42 0.6 10.6 1.24 13.2 4.61
4*4 2 7*0.82 0.8 4.1 2.42 0.6 11.0 1.24 13.6 4.61
4*6 1 1*2.76 0.8 4.5 2.42 0.7 12.2 1.24 14.8 3.08
4*6 2 7*1.01 0.8 4.6 2.42 0.7 12.6 1.24 15.2 3.08
4*10 1 1*3.51 1 5.6 2.42 0.8 15.2 1.24 17.8 1.83
4*10 2 7*1.33 1 6.0 2.42 0.8 16.1 1.24 18.7 1.83
4*16 2 7*1.7 1 7.2 2.42 0.9 19.2 1.24 21.8 1.15
4*25 2 7*2.12 1.2 8.9 2.42 0.9 23.2 1.24 25.8 0.727
4*35 2 7*2.46 1.2 9.9 2.42 0.9 25.7 1.24 28.3 0.524
5*1.5 1 1*1.33 0.8 3.0 2.7 0.6 9.4 1.24 12.0 12.1
5*1.5 2 7*0.52 0.8 3.2 2.7 0.6 9.7 1.24 12.3 12.1
5*2.5 1 1*1.74 0.8 3.4 2.7 0.6 10.5 1.24 13.1 7.41
5*2.5 2 7*0.66 0.8 3.6 2.7 0.6 10.9 1.24 13.4 7.41
5*4 1 1*2.19 0.8 3.9 2.7 0.7 11.9 1.24 14.5 4.61
5*4 2 7*0.82 0.8 4.1 2.7 0.7 12.4 1.24 14.9 4.61
5*6 1 1*2.76 0.8 4.5 2.7 0.8 13.6 1.24 16.2 3.08
5*6 2 7*1.01 0.8 4.6 2.7 0.8 14.1 1.24 16.7 3.08
5*10 1 1*3.51 1 5.6 2.7 0.8 16.7 1.24 19.3 1.83
5*10 2 7*1.33 1 6.0 2.7 0.8 17.8 1.24 20.4 1.83
5*16 2 7*1.7 1 7.2 2.7 0.8 21.0 1.24 23.6 1.15
5*25 2 7*2.12 1.2 8.9 2.7 0.9 25.7 1.24 28.3 0.727
5*35 2 7*2.46 1.2 9.9 2.7 0.9 28.5 1.24 31.1 0.524
3*25/16 2 7*2.12
7*1.7
1.2
1
8.9
7.2
2.42 0.9 22.3 1.24 24.9 0.727
1.15
3*35/16 2 7*2.46
7*1.7
1.2
1
9.9
7.2
2.42 0.9 24.1 1.24 26.7 0.524
1.15


Edit Table


Nominal cross section of conductors mm2 Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness mm Nominal diameter of insulation
mm
k Approximate thickness of filler
mm
Approximate diameter of filler
mm
Minimum sheath thickness
mm
Average overall dimensions
mm
Maximum ohmic resistance of the conductor at 20°C Ω/km
2*10 2 7*1.33 1 6.1 2 0.6 13.4 1.24 16.0 3.08
2*16 2 7*1.7 1 7.2 2 0.6 15.6 1.24 18.2 1.91
2*25 2 7*2.1 1.2 8.8 2 0.7 19.0 1.24 21.6 1.2
2*35 2 7*2.42 1.2 9.8 2 0.7 20.9 1.24 23.5 0.868
3*10 2 7*1.33 1 6.1 2.16 0.6 14.4 1.24 16.9 3.08
3*16 2 7*1.7 1 7.2 2.16 0.7 17.0 1.24 19.5 1.91
3*25 2 7*2.1 1.2 8.8 2.16 0.8 20.6 1.24 23.2 1.2
3*35 2 7*2.42 1.2 9.8 2.16 0.8 22.7 1.24 25.3 0.868
4*10 2 7*1.33 1 6.1 2.42 0.7 16.1 1.24 18.7 3.08
4*16 2 7*1.7 1 7.2 2.42 0.8 19.0 1.24 21.6 1.91
4*25 2 7*2.1 1.2 8.8 2.42 0.9 23.1 1.24 25.7 1.2
4*35 2 7*2.42 1.2 9.8 2.42 0.9 25.4 1.24 28.0 0.868
3*25/16 2 7*2.1 | 7*1.7 1.2
1
8.8 | 7.2 2.42 0.9 22.1 1.24 24.7 1.2 | 1.91
3*35/16 2 7*2.42 | 7*1.7 1.2
1
9.76 | 7.2 2.42 0.9 23.9 1.24 26.5 0.868 | 1.91


Edit Table

Cenelec

NYY-O
NYY-J
NAYY-O
NAYY-J
NA2XY
N2XY

Name in related standard

Multi Core Power Cables

Nominal Voltage U0/U

0.6/1 KV

Reference standard

IEC 60502 – 1

Standard code

IEC 60502 – 1

Tempreture range

PVC: -30℃ to +70℃
XLPE: -40℃ to +90℃

Cable Layer Construction

Cu/PVC/PVC
AL/PVC/PVC
AL/XLPE/PVC

Conductor material

copper conductor according to IEC 60228, class 1 ( solid ), class 2 ( stranded ) or class 5 ( flexible ).

PVC core insulation

Compound type of PVC / A or XLPE

PVC outer sheath

Compound type of PVC/ ST1.

Filler

PVC

Shield

*

Core insulation color

According to the customer’s request

Sheath color

Sheath color is normally black. According to the customer’s request.

These types of cables are used for distribution of electrical energy for fixed installations in underground, cable

ducts, power stations, indoors, in water and open air where mechanical damages are not expected.



Nominal cross section of conductors mm2 Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness mm Nominal diameter of insulation
mm
k Approximate thickness of filler
mm
Approximate diameter of filler
mm
Minimum sheath thickness
mm
Average overall dimensions
mm
Maximum ohmic resistance of the conductor at 20°C Ω/km
2*1.5 1 1*1.33 0.8 3.0 2 0.6 7.3 1.24 9.8 12.1
2*1.5 2 7*0.52 0.8 3.2 2 0.6 7.5 1.24 10.1 12.1
2*2.5 1 1*1.74 0.8 3.4 2 0.6 8.1 1.24 10.7 7.41
2*2.5 2 7*0.66 0.8 3.6 2 0.6 8.4 1.24 10.9 7.41
2*4 1 1*2.19 0.8 3.9 2 0.6 9.0 1.24 11.6 4.61
2*4 2 7*0.82 0.8 4.1 2 0.6 9.3 1.24 11.9 4.61
2*6 1 1*2.76 0.8 4.5 2 0.6 10.1 1.24 12.7 3.08
2*6 2 7*1.01 0.8 4.6 2 0.6 10.5 1.24 13.0 3.08
2*10 1 1*3.51 1 5.6 2 0.7 12.6 1.24 15.2 1.83
2*10 2 7*1.33 1 6.0 2 0.7 13.4 1.24 16.0 1.83
2*16 2 7*1.7 1 7.2 2.16 0.7 17.0 1.24 19.5 1.15
2*25 2 7*2.12 1.2 8.9 2.16 0.8 20.7 1.24 23.3 0.727
2*35 2 7*2.46 1.2 9.9 2.16 0.8 22.9 1.24 25.5 0.524
3*1.5 1 1*1.33 0.8 3.0 2.16 0.6 7.7 1.24 10.3 12.1
3*1.5 2 7*0.52 0.8 3.2 2.16 0.6 8.0 1.24 10.6 12.1
3*2.5 1 1*1.74 0.8 3.4 2.16 0.6 8.6 1.24 11.2 7.41
3*2.5 2 7*0.66 0.8 3.6 2.16 0.6 8.9 1.24 11.5 7.41
3*4 1 1*2.19 0.8 3.9 2.16 0.6 9.6 1.24 12.2 4.61
3*4 2 7*0.82 0.8 4.1 2.16 0.6 10.0 1.24 12.5 4.61
3*6 1 1*2.76 0.8 4.5 2.16 0.6 10.8 1.24 13.4 3.08
3*6 2 7*1.01 0.8 4.6 2.16 0.6 11.2 1.24 13.8 3.08
3*10 1 1*3.51 1 5.6 2.16 0.7 13.5 1.24 16.1 1.83
3*10 2 7*1.33 1 6.0 2.16 0.7 14.3 1.24 16.9 1.83
3*16 2 7*1.7 1 7.2 2.16 0.9 17.4 1.24 19.9 1.15
3*25 2 7*2.12 1.2 8.9 2.16 0.8 20.7 1.24 23.3 0.727
3*35 2 7*2.46 1.2 9.9 2.16 0.8 22.9 1.24 25.5 0.524
4*1.5 1 1*1.33 0.8 3.0 2.42 0.6 8.5 1.24 11.1 12.1
4*1.5 2 7*0.52 0.8 3.2 2.42 0.6 8.8 1.24 11.4 12.1
4*2.5 1 1*1.74 0.8 3.4 2.42 0.6 9.5 1.24 12.1 7.41
4*2.5 2 7*0.66 0.8 3.6 2.42 0.6 9.9 1.24 12.4 7.41
4*4 1 1*2.19 0.8 3.9 2.42 0.6 10.6 1.24 13.2 4.61
4*4 2 7*0.82 0.8 4.1 2.42 0.6 11.0 1.24 13.6 4.61
4*6 1 1*2.76 0.8 4.5 2.42 0.7 12.2 1.24 14.8 3.08
4*6 2 7*1.01 0.8 4.6 2.42 0.7 12.6 1.24 15.2 3.08
4*10 1 1*3.51 1 5.6 2.42 0.8 15.2 1.24 17.8 1.83
4*10 2 7*1.33 1 6.0 2.42 0.8 16.1 1.24 18.7 1.83
4*16 2 7*1.7 1 7.2 2.42 0.9 19.2 1.24 21.8 1.15
4*25 2 7*2.12 1.2 8.9 2.42 0.9 23.2 1.24 25.8 0.727
4*35 2 7*2.46 1.2 9.9 2.42 0.9 25.7 1.24 28.3 0.524
5*1.5 1 1*1.33 0.8 3.0 2.7 0.6 9.4 1.24 12.0 12.1
5*1.5 2 7*0.52 0.8 3.2 2.7 0.6 9.7 1.24 12.3 12.1
5*2.5 1 1*1.74 0.8 3.4 2.7 0.6 10.5 1.24 13.1 7.41
5*2.5 2 7*0.66 0.8 3.6 2.7 0.6 10.9 1.24 13.4 7.41
5*4 1 1*2.19 0.8 3.9 2.7 0.7 11.9 1.24 14.5 4.61
5*4 2 7*0.82 0.8 4.1 2.7 0.7 12.4 1.24 14.9 4.61
5*6 1 1*2.76 0.8 4.5 2.7 0.8 13.6 1.24 16.2 3.08
5*6 2 7*1.01 0.8 4.6 2.7 0.8 14.1 1.24 16.7 3.08
5*10 1 1*3.51 1 5.6 2.7 0.8 16.7 1.24 19.3 1.83
5*10 2 7*1.33 1 6.0 2.7 0.8 17.8 1.24 20.4 1.83
5*16 2 7*1.7 1 7.2 2.7 0.8 21.0 1.24 23.6 1.15
5*25 2 7*2.12 1.2 8.9 2.7 0.9 25.7 1.24 28.3 0.727
5*35 2 7*2.46 1.2 9.9 2.7 0.9 28.5 1.24 31.1 0.524
3*25/16 2 7*2.12
7*1.7
1.2
1
8.9
7.2
2.42 0.9 22.3 1.24 24.9 0.727
1.15
3*35/16 2 7*2.46
7*1.7
1.2
1
9.9
7.2
2.42 0.9 24.1 1.24 26.7 0.524
1.15


Edit Table


Nominal cross section of conductors mm2 Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness mm Nominal diameter of insulation
mm
k Approximate thickness of filler
mm
Approximate diameter of filler
mm
Minimum sheath thickness
mm
Average overall dimensions
mm
Maximum ohmic resistance of the conductor at 20°C Ω/km
2*10 2 7*1.33 1 6.1 2 0.6 13.4 1.24 16.0 3.08
2*16 2 7*1.7 1 7.2 2 0.6 15.6 1.24 18.2 1.91
2*25 2 7*2.1 1.2 8.8 2 0.7 19.0 1.24 21.6 1.2
2*35 2 7*2.42 1.2 9.8 2 0.7 20.9 1.24 23.5 0.868
3*10 2 7*1.33 1 6.1 2.16 0.6 14.4 1.24 16.9 3.08
3*16 2 7*1.7 1 7.2 2.16 0.7 17.0 1.24 19.5 1.91
3*25 2 7*2.1 1.2 8.8 2.16 0.8 20.6 1.24 23.2 1.2
3*35 2 7*2.42 1.2 9.8 2.16 0.8 22.7 1.24 25.3 0.868
4*10 2 7*1.33 1 6.1 2.42 0.7 16.1 1.24 18.7 3.08
4*16 2 7*1.7 1 7.2 2.42 0.8 19.0 1.24 21.6 1.91
4*25 2 7*2.1 1.2 8.8 2.42 0.9 23.1 1.24 25.7 1.2
4*35 2 7*2.42 1.2 9.8 2.42 0.9 25.4 1.24 28.0 0.868
3*25/16 2 7*2.1 | 7*1.7 1.2
1
8.8 | 7.2 2.42 0.9 22.1 1.24 24.7 1.2 | 1.91
3*35/16 2 7*2.42 | 7*1.7 1.2
1
9.76 | 7.2 2.42 0.9 23.9 1.24 26.5 0.868 | 1.91


Edit Table

[ninja_tables id=”19054″][ninja_tables id=”19062″]

coaxial cables

Coaxial 01




VDE Code

*

Peak Working Voltage

*

Max. conductor resistance

*

Max. mutual capacitance

*

Min. insulation resistance

10,000MΩ.Km

Reference Standard

JIS C 3501
IEC 60096

Temperature Range

−30 ℃ to +70 ℃

Cable Layer Construction

Cu/FPE/Al Foil/TCWB/PVC

Conductor material

Plain or tinned copper conductor according to IEC 60228, class 1 (solid), class 2 (stranded).

PE core insulation

Polyethylene, solid or foamed.

PVC outer sheath

Compound type of PVC.

Foil

AL

Shield

CU

Earth

*

Core insulation color

White

Sheath color

White

These types of cables are used in high frequency transmissions specially for transmitters and receivers, computers, radio and TV transmissions.


product type Number and nominal diameter of the conductor (mm) Nominal diameter on insulation (mm) The number and diameter of the shield string conductor material insulating material Characteristic impedance (Ω) Attenuation at 1000 MHz (db) External diameter (mm) Approximate weight (kg/km)
2.5c-2v 1×0.5 2.5 96×0.12 annealed copper Solid polyethylene 75 52 4 22
3c-2v 1×0.5 3 96×0.12 annealed copper Solid polyethylene 75 42 5.5 40
4.5c-2v 1×0.9 4.5 96×0.12 annealed copper Foamed polyethylene 75 22 6.5 45
5c-2v 1×0.8 5 96×0.12 annealed copper Foamed polyethylene 75 27 7.5 71
RG6 1×0.90 4.3 96×0.12 annealed copper Foamed polyethylene 75 8.8 5.7 48
RG59 1×0.6 3.5 128×0.12 annealed copper Solid polyethylene 75 11.5 5.5 52


Edit Table

VDE Code

*

Peak Working Voltage

*

Max. conductor resistance

*

Max. mutual capacitance

*

Min. insulation resistance

10,000MΩ.Km

Reference Standard

JIS C 3501
IEC 60096

Temperature Range

−30 ℃ to +70 ℃

Cable Layer Construction

Cu/FPE/Al Foil/TCWB/PVC

Conductor material

Plain or tinned copper conductor according to IEC 60228, class 1 (solid), class 2 (stranded).

PE core insulation

Polyethylene, solid or foamed.

PVC outer sheath

Compound type of PVC.

Foil

AL

Shield

CU

Earth

*

Core insulation color

White

Sheath color

White

These types of cables are used in high frequency transmissions specially for transmitters and receivers, computers, radio and TV transmissions.

[ninja_tables id=”19010″]

Indoor Telephone Cables

indoor Telphone 01 scaled




VDE Code

J-2Y (St) Y

Peak Working Voltage

300V (DC)

Max. conductor resistance

:for 0.6mm 65Ω/km

Max. mutual capacitance

52±4nf/Km

Min. insulation resistance

20,000MΩ.Km

Reference Standard

TCI
VDE 0816

Temperature Range

−40 ℃ to +90 ℃

Cable Layer Construction

Cu/HDPE/OSCR/PVC

Conductor material

Solid annealed CU conductor with smooth and uniform surface.

PE core insulation

HDPE compound

PVC outer sheath

PVC/ST1

Foil

AL

Shield

*

Earth

Solid annealed CU conductor with smooth and uniform surface.

Core insulation coalor

According to TCI

Sheath color

Gray

1-These types of cables are used for transmission of analog or digital signals and also for fixed installations. In communications technology the following connections can be installed:

Telephone, Telefax as well as standard modems of postal services, alarm systems for burglary and fire, communications and paging systems, access control, time and data control systems.

2- It is not allowed to use it permanently under or on the wall as well as under the ground.


product type Nominal diameter of the conductor (mm) insulating material Nominal insulation thickness (mm) Nominal sheath thickness (mm) Average overall dimensions (mm) Approximate weight (kg/km)
2×2×0.6 0.6 HDPE 0.2 0.8 4.8 29
4×2×0.6 0.6 HDPE 0.2 0.8 6.1 45
6×2×0.6 0.6 HDPE 0.2 0.8 6.7 60
10×2×0.6 0.6 HDPE 0.2 1 8.1 90


Edit Table

VDE Code

J-2Y (St) Y

Peak Working Voltage

300V (DC)

Max. conductor resistance

:for 0.6mm 65Ω/km

Max. mutual capacitance

52±4nf/Km

Min. insulation resistance

20,000MΩ.Km

Reference Standard

TCI
VDE 0816

Temperature Range

−40 ℃ to +90 ℃

Cable Layer Construction

Cu/HDPE/OSCR/PVC

Conductor material

Solid annealed CU conductor with smooth and uniform surface.

PE core insulation

HDPE compound

PVC outer sheath

PVC/ST1

Foil

AL

Shield

*

Earth

Solid annealed CU conductor with smooth and uniform surface.

Core insulation coalor

According to TCI

Sheath color

Gray

1-These types of cables are used for transmission of analog or digital signals and also for fixed installations. In communications technology the following connections can be installed:

Telephone, Telefax as well as standard modems of postal services, alarm systems for burglary and fire, communications and paging systems, access control, time and data control systems.

2- It is not allowed to use it permanently under or on the wall as well as under the ground.

[ninja_tables id=”19015″]

Outdoor Telephone Cables

Outdoor Telphone 03




VDE Code

A-2Y (St) 2Y

Peak Working Voltage

225V (DC)

Max. conductor resistance

:for 0.6mm 65Ω/km

Max. mutual capacitance

52±4nf/Km

Min. insulation resistance

20,000MΩ.Km

Reference Standard

TCI
VDE 0816

Temperature Range

−40 ℃ to +90 ℃

Cable Layer Construction

Cu/HDPE/OSCR/HDPE

Conductor material

Solid annealed CU conductor with smooth and uniform surface.

PE core insulation

HDPE compound

PVC outer sheath

PE

Foil

AL

Shield

*

Earth

Solid annealed CU conductor with smooth and uniform surface.

Core insulation coalor

According to TCI

Sheath color

Black

These types of cables are used for transmission of analog or digital signals and also for fixed installations. All outdoor cables are principally suitable for installation in most types of plants.

product type Nominal diameter of the conductor (mm) insulating material Nominal insulation thickness (mm) Nominal sheath thickness (mm) Average overall dimensions (mm) Approximate weight (kg/km)
2×2×0.6 0.6 HDPE 0.2 0.8 4.8 26
4×2×0.6 0.6 HDPE 0.2 0.8 6.1 42
6×2×0.6 0.6 HDPE 0.2 0.8 6.7 57
10×2×0.6 0.6 HDPE 0.2 1 8.1 85


Edit Table

VDE Code

A-2Y (St) 2Y

Peak Working Voltage

225V (DC)

Max. conductor resistance

:for 0.6mm 65Ω/km

Max. mutual capacitance

52±4nf/Km

Min. insulation resistance

20,000MΩ.Km

Reference Standard

TCI
VDE 0816

Temperature Range

−40 ℃ to +90 ℃

Cable Layer Construction

Cu/HDPE/OSCR/HDPE

Conductor material

Solid annealed CU conductor with smooth and uniform surface.

PE core insulation

HDPE compound

PVC outer sheath

PE

Foil

AL

Shield

*

Earth

Solid annealed CU conductor with smooth and uniform surface.

Core insulation coalor

According to TCI

Sheath color

Black

These types of cables are used for transmission of analog or digital signals and also for fixed installations. All outdoor cables are principally suitable for installation in most types of plants.

[ninja_tables id=”19021″]