Light Inflexible cable 005




Cenelec

H05VV-R & H05VV-U

Name in related standard

Sheathed cables for fixed wiring

Nominal Voltage U0/U

300/500V

Reference standard

IEC 60227-4

Standard code

60227 IEC 10

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.

PVC core insulation

Compound type of PVC/ C.

PVC outer sheath

Compound type of PVC/ ST4.

Filler

PVC

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black.

1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.

Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Approximate thickness of filler mm Nominal sheath thickness (mm) Average overall dimensions (Lower limit) (mm) Average overall dimensions (Upper limit) (mm) Maximum ohmic resistance of the conductor at 20°C (Ω/km) Approximate (weight kg/km)
2×1.5 1 1×1.33 0.7 0.6 1.2 7.6 10 12.1 115
2×1.5 2 7×0.52 0.7 0.6 1.2 7.8 10.5 12.1 124
2×2.5 1 1×1.74 0.8 0.6 1.2 8.6 11.5 7.41 155
2×2.5 2 7×0.66 0.8 0.6 1.2 9 12 7.41 169
2×4 1 1×2.19 0.8 0.6 1.2 9.6 12.5 4.61 200
2×4 2 7×0.82 0.8 0.6 1.2 10 13 4.61 220
2×6 1 1×2.76 0.8 0.6 1.2 10.5 13.5 3.08 260
2×6 2 7×1.01 0.8 0.6 1.2 11 14 1.08 285
2×10 1 1×3.51 1 0.7 1.4 13 16.5 1.83 430
2×10 2 7×1.33 1 0.7 1.4 13.5 17.5 1.83 455
2×16 2 7×1.7 1 0.7 1.4 15.5 20 1.15 630
2×25 2 7×2.12 1.2 1 1.4 18.5 24 0.727 960
2×35 2 7×2.46 1.2 1.1 1.6 21 27.5 0.524 1280
3×1.5 1 1×1.33 0.7 0.6 1.2 8 10.5 12.1 135
3×1.5 2 7×0.52 0.7 0.6 1.2 8.2 11 12.1 142
3×2.5 1 1×1.74 0.8 0.6 1.2 9.2 12 7.41 185
3×2.5 2 7×0.66 0.8 0.6 1.2 9.4 12.5 7.41 201
3×4 1 1×2.19 0.8 0.6 1.2 10 13 4.61 246
3×4 2 7×0.82 0.8 0.6 1.2 10.5 13.5 4.61 268
3×6 1 1×2.76 0.8 0.6 1.4 11.5 14.5 3.08 340
3×6 2 7×1.01 0.8 0.6 1.4 12 15.5 3.08 361
3×10 1 1×3.51 1 0.7 1.4 14 17.5 1.83 535
3×10 2 7×1.33 1 0.7 1.4 14.5 19 1.83 568
3×16 2 7×1.7 1 0.9 1.4 16.5 21.5 1.15 815
3×25 2 7×2.12 1.2 1 1.6 20.5 26 0.727 1230
3×35 2 7×2.46 1.2 1.1 1.6 22 29 0.524 1620
4×1.5 1 1×1.33 0.7 0.6 1.2 8.6 11.5 12.1 161
4×1.5 2 7×0.52 0.7 0.6 1.2 9 12 12.1 172
4×2.5 1 1×1.74 0.8 0.6 1.2 10 13 7.41 223
4×2.5 2 7×0.66 0.8 0.6 1.2 10 13.5 7.41 242
4×4 1 1×2.19 0.8 0.6 1.4 11.5 14.5 4.61 312
4×4 2 7×0.82 0.8 0.6 1.4 12 15 4.61 338
4×6 1 1×2.76 0.8 0.7 1.4 12.5 16 3.08 421
4×6 2 7×1.01 0.8 0.7 1.4 13 17 3.08 452
4×10 2 7×1.33 1 0.8 1.4 16 20.5 1.83 695
4×16 2 7×1.7 1 0.9 1.4 18 23.5 1.15 1000
4×25 2 7×2.12 1.2 1.1 1.6 22.5 28.5 0.727 1555
4×35 2 7×2.46 1.2 1.2 1.6 24.5 32 0.524 2010
5×1.5 1 1×1.33 0.7 0.6 1.2 9.4 12 12.1 187
5×1.5 2 7×0.52 0.7 0.6 1.2 9.8 12.5 12.1 202
5×2.5 1 1×1.74 0.8 0.6 1.2 11 14 7.41 266
5×2.5 2 7×0.66 0.8 0.6 1.2 11 14.5 7.41 280
5×4 1 1×2.19 0.8 0.7 1.4 12.5 16 4.61 384
5×4 2 7×0.82 0.8 0.7 1.4 13 17 4.61 415
5×6 1 1×2.76 0.8 0.8 1.4 13.5 17.5 3.08 510
5×6 2 7×1.01 0.8 0.8 1.4 14.5 18.5 3.08 540
5×10 1 1×3.51 1 0.8 1.4 17 21 1.83 782
5×10 2 7×1.33 1 0.8 1.4 17.5 22 1.83 830
5×16 2 7×1.7 1 1 1.6 20.5 26 1.15 1225
5×25 2 7×2.12 1.2 1.2 1.6 24.5 31.5 0.727 1860
5×35 2 7×2.46 1.2 1.3 1.6 27 35 0.524 2450


Edit Table

Cenelec

H05VV-R & H05VV-U

Name in related standard

Sheathed cables for fixed wiring

Nominal Voltage U0/U

300/500V

Reference standard

IEC 60227-4

Standard code

60227 IEC 10

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.

PVC core insulation

Compound type of PVC/ C.

PVC outer sheath

Compound type of PVC/ ST4.

Filler

PVC

Shield

*

Core insulation color

According to IEC 60227 – 1.

Sheath color

Sheath color is normally black.

1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.

[ninja_tables id=”18811″]

Light flexible cables

Light Inflexible cable 1




Cenelec

H03VV-F

Name in related standard

Light PVC sheathed cord

Nominal Voltage U0/U

300/300 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 52

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor
according to IEC 60228, class 5

PVC core insulation

Compound type of PVC /D

PVC outer sheath

Compound type of PVC / ST5

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are used as extensions and connecting cables for electrical devices,
2-appliances and machinery where plugs must be permanently connected to the corresponding cables.
Examples: kitchen utensils, desk lamps, floor lamps, vacuum cleaners, office machines, radios and etc. These cables are not permitted to be used for cooking or heating appliances, also they are not suitable for outdoor and industrial use or farming machinery.


Nominal cross section of conductors (mm²) Conductor class The number and diameter of the nominal string of conductors Nominal insulation thickness (mm) Nominal sheath thickness (mm) Average overall dimensions (Lower limit) (mm) Average overall dimensions (Upper limit) (mm) Maximum ohmic resistance of the conductor at 20°C (ohm/km) Approximate weight (kg/km)
2×0.5 5 16×0.193 0.5 0.6 4.6 5.9 39 37
2×0.5 Flat 5 16×0.193 0.5 0.6 4.9×3 5.9×3.7 39 24
2×0.75 5 24×0.193 0.5 0.6 4.9 6.3 26 45
2×0.75 Flat 5 24×0.193 0.5 0.6 5.2×3.2 6.3×3.8 26 30
3×0.5 5 16×0.193 0.5 0.6 4.9 6.3 39 43
3×0.75 5 24×0.193 0.5 0.6 5.2 6.7 26 55


Edit Table

Cenelec

H03VV-F

Name in related standard

Light PVC sheathed cord

Nominal Voltage U0/U

300/300 v

Reference standard

IEC 60227-5

Standard code

60227 IEC 52

Tempreture range

– 30℃ to + 70℃

Cable Layer Construction

Cu/PVC/PVC

Conductor material

Flexible copper conductor
according to IEC 60228, class 5

PVC core insulation

Compound type of PVC /D

PVC outer sheath

Compound type of PVC / ST5

Filler

*

Shield

*

Core insulation color

According to IEC 60227 – 1

Sheath color

Sheath color is normally black, white or as per customer request.

1-These types of cables are used as extensions and connecting cables for electrical devices,
2-appliances and machinery where plugs must be permanently connected to the corresponding cables.
Examples: kitchen utensils, desk lamps, floor lamps, vacuum cleaners, office machines, radios and etc. These cables are not permitted to be used for cooking or heating appliances, also they are not suitable for outdoor and industrial use or farming machinery.