Single-core non-sheathed cable with flexible conductor for general purposes & Single-core non-sheathed cable with flexible conductor for internal wiring for a conductor temperature of 70 °C
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-3
Standard code
60227 IEC 06 ( H05V – K ) 60227 IEC 02 ( H07V – K )
Tempreture range
Flexing: -5℃ to +70℃ Fixed installations: -30℃ to +70℃
Cable Layer Construction
CU/PVC
Conductor material
Flexible copper conductor according to IEC 60228, class 5 (flexible).
PVC core insulation
Compound type of PVC/ C.
PVC outer sheath
*
Filler
*
Shield
*
Core insulation color
According to the customer’s request
Sheath color
*
1-EarthingIndoor or receiver installationsIndoor installations. 2- Premises that contain a bath or shower. 3-Electrical installations in caravans and in caravans parks. 4-These types of cables are used for fixed installations as connecting cables in underground cable ducts, machines and in distribution boards where more flexibility is required. 5-Direct laying on cable trays, channels or tanks is not permitted.
Single-core non-sheathed cable with flexible conductor for general purposes & Single-core non-sheathed cable with flexible conductor for internal wiring for a conductor temperature of 70 °C
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-3
Standard code
60227 IEC 06 ( H05V – K ) 60227 IEC 02 ( H07V – K )
Tempreture range
Flexing: -5℃ to +70℃ Fixed installations: -30℃ to +70℃
Cable Layer Construction
CU/PVC
Conductor material
Flexible copper conductor according to IEC 60228, class 5 (flexible).
PVC core insulation
Compound type of PVC/ C.
PVC outer sheath
*
Filler
*
Shield
*
Core insulation color
According to the customer’s request
Sheath color
*
1-EarthingIndoor or receiver installationsIndoor installations. 2- Premises that contain a bath or shower. 3-Electrical installations in caravans and in caravans parks. 4-These types of cables are used for fixed installations as connecting cables in underground cable ducts, machines and in distribution boards where more flexibility is required. 5-Direct laying on cable trays, channels or tanks is not permitted.
Single-core non-sheathed cable with rigid conductor for general purposes & Single-core non-sheathed cable with solid conductor for internal wiring for a conductor temperature of 70 °C
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-3
Standard code
60227 IEC 05 ( H05V – U )
60227 IEC 01 ( H07V – U )
60227 IEC 01 ( H07V- R )
Tempreture range
– 30℃ to + 70℃
Cable Layer Construction
CU/PVC
Conductor material
Annealed copper conductor
PVC core insulation
PVC/ C
PVC outer sheath
*
Filler
*
Shield
*
Core insulation color
According to the customer’s request
Sheath color
*
1- Outdoor lighting installations.
2- EarthingIndoor or receiver installations.
3- Indoor installations in housing.
Nominal cross section of conductors (mm²)
Conductor class
The number and diameter of the nominal string of conductors
Nominal insulation thickness (mm)
Average overall dimensions (Lower limit) (mm)
Average overall dimensions (Upper limit) (mm)
Maximum ohmic resistance of the conductor at 20°C (Ω/km)
Single-core non-sheathed cable with rigid conductor for general purposes & Single-core non-sheathed cable with solid conductor for internal wiring for a conductor temperature of 70 °C
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-3
Standard code
60227 IEC 05 ( H05V – U )
60227 IEC 01 ( H07V – U )
60227 IEC 01 ( H07V- R )
Tempreture range
– 30℃ to + 70℃
Cable Layer Construction
CU/PVC
Conductor material
Annealed copper conductor
PVC core insulation
PVC/ C
PVC outer sheath
*
Filler
*
Shield
*
Core insulation color
According to the customer’s request
Sheath color
*
1- Outdoor lighting installations.
2- EarthingIndoor or receiver installations.
3- Indoor installations in housing.
copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.
PVC core insulation
Compound type of PVC/ C.
PVC outer sheath
Compound type of PVC/ ST4.
Filler
PVC
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black.
1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.
Nominal cross section of conductors (mm²)
Conductor class
The number and diameter of the nominal string of conductors
Nominal insulation thickness (mm)
Approximate thickness of filler mm
Nominal sheath thickness (mm)
Average overall dimensions (Lower limit) (mm)
Average overall dimensions (Upper limit) (mm)
Maximum ohmic resistance of the conductor at 20°C (Ω/km)
copper conductor according to IEC 60228, class 1( solid ) for conductors up to and including 16 mm², class 2 (stranded) for all sizes of conductors.
PVC core insulation
Compound type of PVC/ C.
PVC outer sheath
Compound type of PVC/ ST4.
Filler
PVC
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black.
1- These types of cables are used under or on plaster, on concrete or brick walls in dry or wet environments.
2-The use of these types of cables in external installations is allowed only if they are not exposed to direct sunlight.
3- These types of cables are not suitable for use in compressed concrete.
Flexible copper conductor according to IEC 60228, class 5.
PVC core insulation
Compound type of PVC/ D.
PVC outer sheath
Compound type of PVC / ST5.
Filler
*
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black, white or as per customer request.
1-Indoor installations in housing.
2-Premises that contain a bath or shower.
3-These types of cables are used in applications such as extensions and connecting cables for electrical devices,
appliances and machinery where plugs must be permanently connected to the corresponding cables.
4-Any direct cable contact with hot parts of cooking and heating appliances and also any other heat influences is
prohibited.
Nominal cross section of conductors (mm²)
Conductor class
The number and diameter of the nominal string of conductors
Nominal insulation thickness (mm)
Nominal sheath thickness (mm)
Average overall dimensions (Lower limit) (mm)
Average overall dimensions (Upper limit) (mm)
Maximum ohmic resistance of the conductor at 20°C (ohm/km)
Flexible copper conductor according to IEC 60228, class 5.
PVC core insulation
Compound type of PVC/ D.
PVC outer sheath
Compound type of PVC / ST5.
Filler
*
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black, white or as per customer request.
1-Indoor installations in housing.
2-Premises that contain a bath or shower.
3-These types of cables are used in applications such as extensions and connecting cables for electrical devices,
appliances and machinery where plugs must be permanently connected to the corresponding cables.
4-Any direct cable contact with hot parts of cooking and heating appliances and also any other heat influences is
prohibited.
Circular PVC sheathed lift cable and cable for flexible connections
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-6
Standard code
۶۰۲۲۷ IEC 71C
Tempreture range
– 30℃ to + 70℃
Cable Layer Construction
Cu/PVC/PVC
Conductor material
Flexible copper conductor according to IEC 60228, class 5.
PVC core insulation
Compound type of PVC/ D.
PVC outer sheath
Compound type of PVC / ST5.
Filler
*
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black, white or as per customer request.
1-These types of cables are often used as mobile cables for cranes, elevators and conveyor systems.
2- These cables are suitable for use in indoor facilities and their advantages include high flexibility and minimal space requirement.
Nominal cross section of conductors (mm²)
Conductor class
The number and diameter of the nominal string of conductors
Nominal insulation thickness (mm)
Nominal diameter of insulation (mm)
Assumed diameter wire (mm)
K
Assumed diameter under the sheath (mm)
Nominal sheath thickness (mm)
Average overall dimensions (mm)
Maximum ohmic resistance of the conductor at 20°C (ohm/km)
Circular PVC sheathed lift cable and cable for flexible connections
Nominal Voltage U0/U
300 / 500 V for conductors up to and including 1mm²
450 / 750 V for conductors above 1mm²
Reference standard
IEC 60227-6
Standard code
۶۰۲۲۷ IEC 71C
Tempreture range
– 30℃ to + 70℃
Cable Layer Construction
Cu/PVC/PVC
Conductor material
Flexible copper conductor according to IEC 60228, class 5.
PVC core insulation
Compound type of PVC/ D.
PVC outer sheath
Compound type of PVC / ST5.
Filler
*
Shield
*
Core insulation color
According to IEC 60227 – 1.
Sheath color
Sheath color is normally black, white or as per customer request.
1-These types of cables are often used as mobile cables for cranes, elevators and conveyor systems.
2- These cables are suitable for use in indoor facilities and their advantages include high flexibility and minimal space requirement.
Solid annealed CU conductor with smooth and uniform surface.
PE core insulation
HDPE compound
PVC outer sheath
PE
Foil
AL
Shield
*
Earth
Solid annealed CU conductor with smooth and uniform surface.
Core insulation coalor
According to TCI
Sheath color
Black
These types of cables are used for transmission of analog or digital signals and also for fixed installations. All outdoor cables are principally suitable for installation in most types of plants.
Solid annealed CU conductor with smooth and uniform surface.
PE core insulation
HDPE compound
PVC outer sheath
PE
Foil
AL
Shield
*
Earth
Solid annealed CU conductor with smooth and uniform surface.
Core insulation coalor
According to TCI
Sheath color
Black
These types of cables are used for transmission of analog or digital signals and also for fixed installations. All outdoor cables are principally suitable for installation in most types of plants.