Specifications and structure of Afshan wires, according to NOOR wire and cable catalog.

Product features

Technical code
H05V-K ، H07V-K ، NYAF
For conductors up to cross-section ISIRI (607) 06
1 mm2
For conductors with a cross section greater than 1 mm2
ISIRI (607) 02
IEC 60227 06 (H05V - K)
IEC 60227 02 (H07V - K)
NYAF
Rated voltage (V)
For conductors up to 300 / 500 v
1 mm2
For conductors with a cross section greater than 450 / 750 v
1 mm2
Reference standard
ISIRI 607 - 3
ISIRI 60227 - 3
Temperature range (°C)
For flexible installation: up to 5 C
+70 C
For fixed installation: up-30 C
+70 C
Structure of layers
Cu / PVC

General description and specifications

Insulated wires for general use
PVC
: Nominal voltage
For conductors up to 300 / 500 v
1 mm2
For conductors with a cross section greater than 450 / 750 v
1 mm2
: reference standard
ISIRI 607 - 3
ISIRI 60227 - 3
: SIM code
For conductors up to ISIRI (607) 06 cross section
1 mm2
For conductors with a cross section greater than 1 mm2
ISIRI (607) 02
IEC 60227 06 (H05V - K)
IEC 60227 02 (H07V - K)
NYAF
: Temperature range
For flexible installation: up to 5 C
+70 C
For fixed installation: up to 30 C
+70 C

Wire and cable structure

Wire structure
Cu/PVC
(Afshan), according to 5 types and grades of the conductor: grade annealed copper
National standard (IEC 60228) ISIRI 3084
Insulation material: mixed type
PVC
c
Insulation coloring: according to customer request

Applications

General and construction uses
Household electrical appliances and mobile electrical equipment are of the splash type because they must withstand constant movement and bending
Cable of electrical appliances: cable of iron, vacuum cleaner, hair dryer, mixer and microwave, etc
Wiring inside the building: due to the high flexibility of the wiring inside the pipes and ducts, it is much easier to wire with a spray wire than a wire wire.
Industrial uses and machines
Electrical panel: control and distribution panel
Cabling of mobile machines: devices that have a moving arm or oscillating parts, the use of wire sprinklers due to the string structure against vibration and movement.
Repeated is very resistant
Wiring inside electronic equipment
Automotive industry and vehicles

Technical specification table

Technical specifications table — page 7
Nominal cross-sectional area of the conductormm²Conductor classNumber and diameter of conductor strandsNominal thickness of insulationmmLower limit of overall dimensionsmmUpper limit of overall dimensionsmmMaximum conductor ohmic resistance at ۲۰°CΩ/kmApproximate weightkg/km
0.5516 x 0.1930.62.12.5399.2
0.75524 x 0.1930.62.22.72611.8
1531 x 0.1930.62.42.819.514
1.5530 x 0.2350.72.83.413.321
2.5550 x 0.2350.83.44.17.9832
4556 x 0.2850.83.94.84.9545
6584 x 0.2850.84.45.33.365
105144 x 0.28515.76.81.91110
165244 x 0.28516.78.11.21160
255301 x 0.3061.28.410.20.78245
355427 x 0.3061.29.711.70.554345
505602 x 0.3061.411.513.90.386492
705854 x 0.3061.413.2160.272675
Main catalog tables — Product technical referenceجدول اصلی مشخصات فنی Flexible stranded wires